Anonymous Installation and Operation Instructions For Custom Mark III CP Series Oil Fired Unit

Make certain that correct voltage has been supplied to motor and control circuit. Insure that outside air openings are provided in the boiler room for ventilation, and for admission of air for combustion. The free area of such openings should not be less than 7 square inch opening per 100,000 Btuh burner input, or more as required by local codes. Check to see that flue, wiring and water level are in order. Start burner fan motor to prime pump. If pump does not pick up oil within a few minutes, prime the pump with lubricating oil.
Source: Gutenberg

Anonymous Installation and Operation Instructions For Custom Mark III CP Series Oil Fired Unit

The Minimum limit setting for any hot water boiler should be 140 degrees F. in order to prevent corrosion of the flues on the fire side. The burner should be run with the primary control thermostat terminals jumpered and the burner controlled directly from an aquastat keeping the boiler hot all the time, thus eliminating the sweating of the flues on the fire side caused by starting from a cold start.
BELT ADJUSTMENT
The proper tension on the fuel unit belt drive is set at the factory. However, the belt should be checked periodically to see that the setting is maintained.
Source: Gutenberg